Table 182: Station authority level “L,S,R” using CONTROL function block
L/R Control L/R Control status Control access
Control FB input
CTRL.LLN0.LocSta
1)
CTRL.LLN0.MltLev L/R state
CTRL.LLN0.LocKeyHMI
Local user IEC 61850
client
2)
IEC 61850
client
3)
CTRL_OFF FALSE FALSE 0
CTRL_LOC FALSE FALSE 1 x
CTRL_STA TRUE FALSE 3 x
CTRL_REM
4)
TRUE FALSE 3 x
CTRL_REM FALSE FALSE 2 x
CTRL_ALL FALSE FALSE 0
1) Station client reserves the control operating by writing controllable point LocSta.
2) Client IEC 61850 command originator category is remote.
3) Client IEC 61850 command originator category is station.
4) CTRL_STA unconnected in application configuration. Station client reserves the control operating by writing controllable point LocSta.
3.17.10.7 Station authority level “L,S,S+R,L+S,L+S+R”
Station authority level “L,S,S+R,L+S,L+S+R” adds station control access together with
several different multilevel access scenarios. Control access can also be simultaneously
permitted from local, station or remote location. Simultaneous local, station or remote
control operation is not allowed as one client and location at time can access controllable
objects and they remain reserved until the previously started control operation is first
completed by the client.
IED
IEC 61850
remote
IEC 61850
station
IEC 61850
remote
IEC 61850
remote
IEC 61850
remote
IED
IEC 61850
station
IED
IEC 61850
station
IED
IEC 61850
station
L+SLOCAL STATION S+R
IEC 61850
remote
IEC 61850
remote
IED
IEC 61850
station
IED
IEC 61850
station
OFFL+S+R
GUID-3F4E6CD7-A89E-4057-8E25-8846B5387C82 V1 EN
Figure 96: Station authority is “L,S,S+R,L+S,L+S+R”
When station authority level “L,S,S+R,L+S,L+S+R” is used, control access can be
selected using R/L button or CONTROL function block. IEC 61850 data object
CTRL.LLN0.LocSta and CONTROL function block input CTRL_STA are applicable for
this station authority level.