OFFLOCAL REMOTE STATION
GUID-7BC51FAF-B097-4CD9-AFF4-6D1F3D548C7F V1 EN
Figure 95: Station authority is “L,S,R”
When the station authority level “L,S,R” is used, the control access can be selected using
R/L button or CONTROL function block. IEC 61850 data object CTRL.LLN0.LocSta
and CONTROL function block input CTRL_STA are applicable for this station authority
level.
Station control access can be reserved by using R/L button or CONTROL function block
together with IEC 61850 data object CTRL.LLN0.LocSta.
Table 181: Station authority level “L,S,R” using R/L button
L/R Control
L/R Control status Control access
R/L button
CTRL.LLN0.LocSta
1)
CTRL.LLN0.MltLev L/R state
CTRL.LLN0.LocKeyHMI
Local user IEC 61850
client
2)
IEC 61850
client
3)
Local FALSE FALSE 1 x
Remote FALSE FALSE 2 x
Remote TRUE FALSE 3 x
Off FALSE FALSE 0
1) Station client reserves the control operating by writing controllable point LocSta.
2) Client IEC 61850 command originator category is remote.
3) Client IEC 61850 command originator category is station.