ABB 615 Series - RTD Temperature Vs. Resistance; Rtd;Ma Input Connection

ABB 615 Series
1196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Since the function can be utilized in various measurement modes, the
default values are set to the extremes; thus, it is very important to set
correct limit values to suit the application before the deadband supervision
works properly.
3.13.2.9 RTD temperature vs. resistance
Table 56: Temperature vs. resistance
Temp
°C
Platinum TCR 0.00385 Nickel TCR 0.00618 Copper TCR
0.00427
Pt 100 Pt 250 Ni 100 Ni 120 Ni 250 Cu 10
-40 84.27 210.675 79.1 94.92 197.75 7.49
-30 88.22 220.55 84.1 100.92 210.25 -
-20 92.16 230.4 89.3 107.16 223.25 8.263
-10 96.09 240.225 94.6 113.52 236.5 -
0 100 250 100 120 250 9.035
10 103.9 259.75 105.6 126.72 264 -
20 107.79 269.475 111.2 133.44 278 9.807
30 111.67 279.175 117.1 140.52 292.75 -
40 115.54 288.85 123 147.6 307.5 10.58
50 119.4 298.5 129.1 154.92 322.75 -
60 123.24 308.1 135.3 162.36 338.25 11.352
70 127.07 317.675 141.7 170.04 354.25 -
80 130.89 327.225 148.3 177.96 370.75 12.124
90 134.7 336.75 154.9 185.88 387.25 -
100 138.5 346.25 161.8 194.16 404.5 12.897
120 146.06 365.15 176 211.2 440 13.669
140 153.58 383.95 190.9 229.08 477.25 14.442
150 - - 198.6 238.32 496.5 -
160 161.04 402.6 206.6 247.92 516.5 15.217
180 168.46 421.15 223.2 267.84 558 -
200 175.84 439.6 240.7 288.84 601.75 -
3.13.2.10 RTD/mA input connection
RTD inputs can be used with a 2-wire or 3-wire connection with common ground. When
using the 3-wire connection, it is important that all three wires connecting the sensor are
Section 3 1MAC059074-MB A
Basic functions
120 615 series ANSI
Technical Manual