Table 548: 47U,27PS Output signals
Name Type Description
TRIP BOOLEAN Trip
PICKUP BOOLEAN Pickup
4.5.5.7 Settings
Table 549: 47U,27PS Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Pickup value 0.010...1.200 xUn 0.001 0.500 Pickup value
Trip delay time 40...120000 ms 10 40 Trip delay time
Table 550: 47U,27PS Group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Voltage block value 0.01...1.00 xUn 0.01 0.20 Internal blocking level
Enable block value 0=False
1=True
1=True Enable Internal Blocking
Table 551: 47U,27PS Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Table 552: 47U,27PS Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
Relative hysteresis 1.0...5.0 % 0.1 4.0 Relative hysteresis for operation
4.5.5.8 Monitored data
Table 553: 47U,27PS Monitored data
Name
Type Values (Range) Unit Description
PICKUP_DUR FLOAT32 0.00...100.00 % Ratio of pickup time / trip time
47U,27PS Enum 1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
Section 4 1MAC059074-MB A
Protection functions
640 615 series ANSI
Technical Manual