Parameter Values (Range) Unit Step Default Description
Amplitude corr. A 0.9000...1.1000 0.0001 1.0000 Phase A Voltage phasor magnitude correction
of an external voltage transformer
Amplitude corr. B 0.9000...1.1000 0.0001 1.0000 Phase B Voltage phasor magnitude correction
of an external voltage transformer
Amplitude corr. C 0.9000...1.1000 0.0001 1.0000 Phase C Voltage phasor magnitude correction
of an external voltage transformer
Division ratio 1000...20000 1 10000 Voltage sensor division ratio
Voltage input type 1=Voltage trafo
3=CVD sensor
1=Voltage trafo Type of the voltage input
Angle Corr A -20.0000...20.0000 deg 0.0001 0.0000 Phase A Voltage phasor angle correction of an
external voltage transformer
Angle Corr B -20.0000...20.0000 deg 0.0001 0.0000 Phase B Voltage phasor angle correction of an
external voltage transformer
Angle Corr C -20.0000...20.0000 deg 0.0001 0.0000 Phase C Voltage phasor angle correction of an
external voltage transformer
3.14.3.6 Monitored data
Monitored data is available in three locations.
• Monitoring/I/O status/Analog inputs
• Monitoring/IED status/SMV traffic
• Monitoring/IED status/SMV accuracy
3.14.4 RESTVTR function block
3.14.4.1 Function block
GUID-9C7DCCB2-018C-4DB3-9F70-30E2B411FD6F V1 EN
Figure 45: Function block
3.14.4.2 Functionality
The RESTVTR function is used in the receiver application to perform the supervision for
the sampled values of analog residual voltage and to connect the received analog residual
voltage input to the application. Synchronization accuracy, sampled value frame transfer
delays and missing frames are being supervised.