3.17.10 Local/remote control function block CONTROL
3.17.10.1 Function block
GUID-FA386432-3AEF-468D-B25E-D1C5BDA838E3 V3 EN
Figure 92: Function block
3.17.10.2 Functionality
Local/Remote control is by default realized through the R/L button on the front panel. The
control via binary input can be enabled by setting the value of the LR control setting to
"Binary input". The binary input control requires that the CONTROL function is
instantiated in the product configuration.
Local/Remote control supports multilevel access for control operations in substations
according to the IEC 61850 standard. Multilevel control access with separate station
control access level is not supported by other protocols than IEC 61850.
The actual Local/Remote control state is evaluated by the priority scheme on the function
block inputs. If more than one input is active, the input with the highest priority is selected.
The priority order is “off”, “local”, “station”, “remote”, “all”.
The actual state is reflected on the CONTROL function outputs. Only one output is active
at a time.
Table 176: Truth table for CONTROL
Input
Output
CTRL_OFF CTRL_LOC CTRL_STA CTRL_REM CTRL_ALL
TRUE N/A N/A N/A N/A OFF = TRUE
FALSE TRUE N/A N/A N/A LOCAL =
TRUE
FALSE FALSE TRUE N/A N/A STATION =
TRUE
FALSE FALSE FALSE TRUE TRUE REMOTE =
TRUE
FALSE FALSE FALSE FALSE TRUE ALL = TRUE
FALSE FALSE FALSE FALSE FALSE OFF = TRUE