3.17.10.8 Signals
Table 185: CONTROL input signals
Name
Type Default Description
CTRL_OFF BOOLEAN 0 Control input OFF
CTRL_LOC BOOLEAN 0 Control input Local
CTRL_STA BOOLEAN 0 Control input Station
CTRL_REM BOOLEAN 0 Control input Remote
CTRL_ALL BOOLEAN 0 Control input All
Table 186: CONTROL output signals
Name Type Description
OFF BOOLEAN Control output OFF
LOCAL BOOLEAN Control output Local
STATION BOOLEAN Control output Station
REMOTE BOOLEAN Control output Remote
ALL BOOLEAN Control output All
BEH_BLK BOOLEAN Logical device CTRL block status
BEH_TST BOOLEAN Logical device CTRL test status
3.17.10.9 Settings
Table 187: Control settings
Parameter
Values (Range) Unit Step Default Description
LR control 1=LR key
2=Binary input
1=LR key LR control through LR key or binary input
Station authority 1=L,R
2=L,S,R
3=L,R,L+R
4=L,S,S+R,L+S,L
+S+R
1=L,R Control command originator category usage
Control mode 1=Enable
2=Blocked
5=Disable
1=Enable Enabling and disabling control
1MAC059074-MB A Section 3
Basic functions
615 series ANSI 189