“Station” and “Local + Station” control access can be reserved by using R/L button or
CONTROL function block in combination with IEC 61850 data object
CTRL.LLN0.LocSta.
Table 183: Station authority level “L,S,S+R,L+S,L+S+R” using R/L button
L/R Control
L/R Control status Control access
R/L button
CTRL.LLN0.LocSta
1)
CTRL.LLN0.MltLev L/R state
CTRL.LLN0.LocKeyHMI
Local user IEC 61850
client
2)
IEC 61850
client
3)
Local FALSE FALSE 1 x
Remote FALSE TRUE 7 x x
Remote TRUE FALSE 3 x
Local + Remote FALSE TRUE 6 x x x
Local + Remote TRUE TRUE 5 x x
Off FALSE FALSE 0
1) Station client reserves the control operating by writing controllable point LocSta.
2) Client IEC61850 command originator category is remote.
3) Client IEC61850 command originator category is station.
Table 184: Station authority level “L,S,S+R,L+S,L+S+R” using CONTROL function block
L/R Control
L/R Control status Control access
Control FB input
CTRL.LLN0.LocSta
1)
CTRL.LLN0.MltLev L/R state
CTRL.LLN0.LocKeyHMI
Local user IEC 61850
client
2)
IEC 61850
client
3)
CTRL_OFF FALSE FALSE 0
CTRL_LOC FALSE FALSE 1 x
CTRL_STA FALSE FALSE 3 x
CTRL_REM
4)
TRUE TRUE 3 x
CTRL_REM FALSE TRUE 7 x x
CTRL_ALL FALSE TRUE 6 x x x
CTRL_ALL
4)
TRUE TRUE 5 x x
1) Station client reserves the control operating by writing controllable point LocSta.
2) Client IEC61850 command originator category is remote.
3) Client IEC61850 command originator category is station.
4) CTRL_STA unconnected in application configuration. Station client reserves the control operating by writing controllable point LocSta.
Section 3 1MAC059074-MB A
Basic functions
188 615 series ANSI