Table 481: 46 Group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Type of reset curve 1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate Selection of reset curve type
Table 482: 46 Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Curve parameter A 0.0086...120.0000 1 28.2000 Parameter A for customer programmable
curve
Curve parameter B 0.0000...0.7120 1 0.1217 Parameter B for customer programmable
curve
Curve parameter C 0.02...2.00 1 2.00 Parameter C for customer programmable
curve
Curve parameter D 0.46...30.00 1 29.10 Parameter D for customer programmable
curve
Curve parameter E 0.0...1.0 1 1.0 Parameter E for customer programmable
curve
Table 483: 46 Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Minimum trip time 20...60000 ms 1 20 Minimum trip time for IDMT curves
Reset delay time 0...60000 ms 1 20 Reset delay time
4.4.1.8 Monitored data
Table 484: 46 Monitored data
Name
Type Values (Range) Unit Description
PICKUP_DUR FLOAT32 0.00...100.00 % Ratio of pickup time / trip time
46 Enum 1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
Section 4 1MAC059074-MB A
Protection functions
592 615 series ANSI