Table 802: VA,VB,VC Output signals
Name Type Description
HIGH_ALARM BOOLEAN High alarm
HIGH_WARN BOOLEAN High warning
LOW_WARN BOOLEAN Low warning
LOW_ALARM BOOLEAN Low alarm
8.1.5.4 Settings
Table 803: VA,VB,VC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Num of phases 1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3 Number of phases required by limit supervision
V high high limit 0.00...4.00 xUn 1 1.40 High alarm voltage limit
V high limit 0.00...4.00 xUn 1 1.20 High warning voltage limit
V low limit 0.00...4.00 xUn 1 0.00 Low warning voltage limit
V low low limit 0.00...4.00 xUn 1 0.00 Low alarm voltage limit
V deadband 100...100000 1 10000 Deadband configuration value for integral
calculation. (percentage of difference between
min and max as 0,001 % s)
Table 804: VA,VB,VC Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Measurement mode 1=RMS
2=DFT
2=DFT Selects used measurement mode
8.1.5.5 Monitored data
Table 805: VA,VB,VC Monitored data
Name
Type Values (Range) Unit Description
VAB-kV FLOAT32 0.00...4.00 xUn Measured phase to phase
voltage amplitude phase AB
VBC-kV FLOAT32 0.00...4.00 xUn Measured phase to phase
voltage amplitude phase BC
VCA-kV FLOAT32 0.00...4.00 xUn Measured phase to phase
voltage amplitude phase CA
Table continues on next page
1MAC059074-MB A Section 8
Measurement functions
615 series ANSI 911
Technical Manual