8.1.11.4 Settings
Table 838: P,E Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Power unit Mult 3=Kilo
6=Mega
3=Kilo Unit multiplier for presentation of the power
related values
Energy unit Mult 3=Kilo
6=Mega
3=Kilo Unit multiplier for presentation of the energy
related values
Active power Dir 1=Forward
2=Reverse
1=Forward Direction of active power flow: Forward,
Reverse
Reactive power Dir 1=Forward
2=Reverse
1=Forward Direction of reactive power flow: Forward,
Reverse
Table 839: P,E Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Forward Wh Initial 0...999999999 1 0 Preset Initial value for forward active energy
Reverse Wh Initial 0...999999999 1 0 Preset Initial value for reverse active energy
Forward VArh Initial 0...999999999 1 0 Preset Initial value for forward reactive energy
Reverse VArh Initial 0...999999999 1 0 Preset Initial value for reverse reactive energy
8.1.11.5 Monitored data
Table 840: P,E Monitored data
Name
Type Values (Range) Unit Description
S-kVA FLOAT32 -999999.9...9999
99.9
kVA Total Apparent Power
P-kW FLOAT32 -999999.9...9999
99.9
kW Total Active Power
Q-kVAr FLOAT32 -999999.9...9999
99.9
kVAr Total Reactive Power
PF FLOAT32 -1.00...1.00 Average Power factor
RSTACM BOOLEAN 0=False
1=True
Reset of accumulated energy
reading
S-kVA FLOAT32 -999999.9...9999
99.9
kVA Total Apparent Power
S_DB FLOAT32 -999999.9...9999
99.9
kVA Apparent power, magnitude of
reported value
S_DMD FLOAT32 -999999.9...9999
99.9
kVA Demand value of apparent
power
Table continues on next page
Section 8 1MAC059074-MB A
Measurement functions
928 615 series ANSI
Technical Manual