Name Type Values (Range) Unit Description
P-kW FLOAT32 -999999.9...9999
99.9
kW Active power, magnitude of
instantaneous value
P_DB FLOAT32 -999999.9...9999
99.9
kW Active power, magnitude of
reported value
P_DMD FLOAT32 -999999.9...9999
99.9
kW Demand value of active power
Q-kVAr FLOAT32 -999999.9...9999
99.9
kVAr Total Reactive Power
Q_DB FLOAT32 -999999.9...9999
99.9
kVAr Reactive power, magnitude of
reported value
Q_DMD FLOAT32 -999999.9...9999
99.9
kVAr Demand value of reactive
power
PF FLOAT32 -1.00...1.00 Average Power factor
PF_DB FLOAT32 -1.00...1.00 Power factor, magnitude of
reported value
PF_DMD FLOAT32 -1.00...1.00 Demand value of power factor
EA_RV_ACM INT64 0...999999999 kWh Accumulated reverse active
energy value
ER_RV_ACM INT64 0...999999999 kVArh Accumulated reverse reactive
energy value
EA_FWD_ACM INT64 0...999999999 kWh Accumulated forward active
energy value
ER_FWD_ACM INT64 0...999999999 kVArh Accumulated forward reactive
energy value
Max demand S FLOAT32 -999999.9...9999
99.9
kVA Maximum demand value of
apparent power
Min demand S FLOAT32 -999999.9...9999
99.9
kVA Minimum demand value of
apparent power
Max demand P FLOAT32 -999999.9...9999
99.9
kW Maximum demand value of
active power
Min demand P FLOAT32 -999999.9...9999
99.9
kW Minimum demand value of
active power
Max demand Q FLOAT32 -999999.9...9999
99.9
kVAr Maximum demand value of
reactive power
Min demand Q FLOAT32 -999999.9...9999
99.9
kVAr Minimum demand value of
reactive power
Time max dmd S Timestamp Time of maximum demand
Time min dmd S Timestamp Time of minimum demand
Time max dmd P Timestamp Time of maximum demand
Time min dmd P Timestamp Time of minimum demand
Time max dmd Q Timestamp Time of maximum demand
Time min dmd Q Timestamp Time of minimum demand
1MAC059074-MB A Section 8
Measurement functions
615 series ANSI 929
Technical Manual