Table 857: 84T Output signals
Name Type Description
TAP_POS INT8 Tap position indication
8.3.7 Settings
Table 858: 84T Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Operation mode 1=NAT2INT
2=BCD2INT
3=GRAY2INT
2=BCD2INT Operation mode selection
8.3.8 Monitored data
Table 859: 84T Monitored data
Name Type Values (Range) Unit Description
BI0 BOOLEAN 0=False
1=True
Binary input 1
BI1 BOOLEAN 0=False
1=True
Binary input 2
BI2 BOOLEAN 0=False
1=True
Binary input 3
BI3 BOOLEAN 0=False
1=True
Binary input 4
BI4 BOOLEAN 0=False
1=True
Binary input 5
BI5 BOOLEAN 0=False
1=True
Binary input 6
SIGN_BIT BOOLEAN 0=False
1=True
Binary input sign bit
END_POS_R BOOLEAN 0=False
1=True
End position raise or highest
allowed tap position reached
END_POS_L BOOLEAN 0=False
1=True
End position lower or lowest
allowed tap position reached
TAP_POS INT8 -63...63 Tap position indication