Table 881: Status indication
Input Status Output
POSOPEN POSCLOSE POSITION
(Monitored data)
OKPOS OPENPOS CLOSEPOS
1=True 0=False 1=Open 1=True 1=True 0=False
0=False 1=True 2=Closed 1=True 0=False 1=True
1=True 1=True 3=Faulty/Bad
(11)
0=False 0=False 0=False
0=False 0=False 0=Intermediat
e (00)
0=False 0=False 0=False
9.2.5 Application
In the field of distribution and sub-transmission automation, the reliable control and status
indication of primary switching components both locally and remotely is in a significant
role. These features are needed especially in modern remote controlled substations. The
application area of 52-TOC, 29DS and 29GS functions covers remote and local status
indication of, for example, disconnectors, air-break switches and grounding switches,
which represent the lowest level of power switching devices without short-circuit
breaking capability.
9.2.6 Signals
Table 882: 52-TOC,29DS Input signals
Name
Type Default Description
POSOPEN BOOLEAN 0=False
Signal for open position of apparatus from I/O
1)
POSCLOSE BOOLEAN 0=False
Signal for close position of apparatus from I/O
1)
1) Not available for monitoring
Table 883: 29GS Input signals
Name
Type Default Description
POSOPEN BOOLEAN 0=False
Signal for open position of apparatus from I/O
1)
POSCLOSE BOOLEAN 0=False
Signal for close position of apparatus from I/O
1)
1) Not available for monitoring