Table 670: INR Output signals
Name Type Description
BLK2H BOOLEAN Second harmonic based block
5.1.7 Settings
Table 671: INR Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Pickup value 5...100 % 1 20 Ratio of the 2. to the 1. harmonic leading to
restraint
Trip delay time 20...60000 ms 1 20 Trip delay time
Table 672: INR Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Table 673: INR Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
5.1.8 Monitored data
Table 674: INR Monitored data
Name
Type Values (Range) Unit Description
INR Enum 1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
1MAC059074-MB A Section 5
Protection related functions
615 series ANSI 771
Technical Manual