GUID-59F4E262-44C8-4EF3-A352-E6358C84C791 V2 EN
Figure 422: An example of the ALARM output use
5.7.4.5 Recorded data
All the information required for a later fault analysis is recorded to 21FL recorded data. In
the protection relay, recorded data is found in Monitoring/Recorded data/Other
protection/S21FL.
The function has also monitored data values which are used for the read-out of continuous
calculation values. The cross reference table shows which of the recorded data values are
available as continuous monitoring values during a fault.
Table 716: Cross reference table for recorded and monitored data values
Recorded data
Monitored data
Flt loop FAULT_LOOP
Flt distance FLT_DISTANCE
Flt Dist quality FLT_DIST_Q
Flt loop resistance RFLOOP
Flt loop reactance XFLOOP
Flt phase reactance XFPHASE
Flt point resistance RF
Flt to Lod Cur ratio IFLT_PER_ILD
Equivalent load Dis S_CALC
XC0F Calc XC0F_CALC
Section 5 1MAC059074-MB A
Protection related functions
824 615 series ANSI