Name Type Values (Range) Unit Description
V_DMD_A FLOAT32 0.00...5.00 xUn Demand value of VA voltage
V_INST_B FLOAT32 0.00...5.00 xUn VB Amplitude, magnitude of
instantaneous value
V_ANGL_B FLOAT32 -180.00...180.00 deg VB angle
V_DMD_B FLOAT32 0.00...5.00 xUn Demand value of VB voltage
V_INST_C FLOAT32 0.00...5.00 xUn VC Amplitude, magnitude of
instantaneous value
V_ANGL_C FLOAT32 -180.00...180.00 deg VC angle
V_DMD_C FLOAT32 0.00...5.00 xUn Demand value of VC voltage
8.1.5.6 Technical data
Table 806: VA, VB, VC Technical data
Characteristic Value
Operation accuracy Depending on the frequency of the voltage
measured: f
n
±2 Hz
At voltages in range 0.01…1.15 × V
n
±0.5% or ±0.002 × V
n
Suppression of harmonics DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
RMS: No suppression
8.1.5.7 Technical revision history
Table 807: VA, VB, VC Technical revision history
Technical revision
Change
B Phase and phase-to-phase voltage angle values and
demand values added to Monitored data view.
C Internal improvement.
D Internal improvement.
8.1.6 Residual current measurement IG
8.1.6.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Residual current measurement RESCMMXU Io IG
1MAC059074-MB A Section 8
Measurement functions
615 series ANSI 913
Technical Manual