5.5.7 Settings
Table 698: BST Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Signal 1 mode 1=on
2=on, logic
included
3=off
2=on, logic
included
Operation mode for signal 1
Signal 2 mode 1=on
2=on, logic
included
3=off
2=on, logic
included
Operation mode for signal 2
Signal 3 mode 1=on
2=on, logic
included
3=off
1=on Operation mode for signal 3
Signal 4 mode 1=on
2=on, logic
included
3=off
1=on Operation mode for signal 4
Signal 5 mode 1=on
2=on, logic
included
3=off
1=on Operation mode for signal 5
Signal 6 mode 1=on
2=on, logic
included
3=off
1=on Operation mode for signal 6
Signal 7 mode 1=on
2=on, logic
included
3=off
1=on Operation mode for signal 7
Signal 8 mode 1=on
2=on, logic
included
3=off
1=on Operation mode for signal 8
Pulse time 1 0...60000 ms 1 0 Minimum pulse time for received signal 1
Pulse time 2 0...60000 ms 1 0 Minimum pulse time for received signal 2
Pulse time 3 0...60000 ms 1 0 Minimum pulse time for received signal 3
Pulse time 4 0...60000 ms 1 0 Minimum pulse time for received signal 4
Pulse time 5 0...60000 ms 1 0 Minimum pulse time for received signal 6
Pulse time 6 0...60000 ms 1 0 Minimum pulse time for received signal 6
Pulse time 7 0...60000 ms 1 0 Minimum pulse time for received signal 7
Pulse time 8 0...60000 ms 1 0 Minimum pulse time for received signal 8
1MAC059074-MB A Section 5
Protection related functions
615 series ANSI 799
Technical Manual