Section 3 Basic functions
3.1 General parameters
Table 5: Analog input settings, phase currents
Parameter Values (Range) Unit Step Default Description
Primary current 1.0...6000.0 A 0.1 100.0 Rated primary current
Secondary current 2=1A
3=5A
2=1A Rated secondary current
Amplitude corr. A 0.9000...1.1000 0.0001 1.0000 Phase A amplitude correction factor
Amplitude corr. B 0.9000...1.1000 0.0001 1.0000 Phase B amplitude correction factor
Amplitude corr. C 0.9000...1.1000 0.0001 1.0000 Phase C amplitude correction factor
Nominal Current
1)
39...4000 A 1 1300 Network Nominal Current (In)
Rated secondary Val
1)
1.000...150.000 mV/Hz 0.001 3.000 Rated Secondary Value (RSV) ratio
Reverse polarity 0=False
1=True
0=False Reverse the polarity of the phase CTs
Angle Corr A -20.0000...20.0000 deg 0.0001 0.0000 Phase A angle correction factor
Angle Corr B -20.0000...20.0000 deg 0.0001 0.0000 Phase B angle correction factor
Angle Corr C -20.0000...20.0000 deg 0.0001 0.0000 Phase C angle correction factor
1) Available for sensor analog inputs only
Table 6: Analog input settings, residual current
Parameter
Values (Range) Unit Step Default Description
Primary current 1.0...6000.0 A 0.1 100.0 Primary current
Secondary current 1=0.2A
2=1A
3=5A
2=1A Secondary current
Amplitude corr. 0.9000...1.1000 0.0001 1.0000 Amplitude correction
Reverse polarity 0=False
1=True
0=False Reverse the polarity of the residual CT
Angle correction -20.0000...20.0000 deg 0.0001 0.0000 Angle correction factor
1MAC059074-MB A Section 3
Basic functions
615 series ANSI 59
Technical Manual