Table 7: Analog input settings, phase voltages
Parameter Values (Range) Unit Step Default Description
Primary voltage 0.100...440.000 kV 0.001 20.000 Primary rated voltage
Secondary voltage 60...210 V 1 100 Secondary rated voltage
VT connection 1=Wye
2=Delta
3=VAB
4=VA
2=Delta Voltage transducer measurement connection
Amplitude corr. A 0.9000...1.1000 0.0001 1.0000 Phase A Voltage phasor magnitude correction
of an external voltage transformer
Amplitude corr. B 0.9000...1.1000 0.0001 1.0000 Phase B Voltage phasor magnitude correction
of an external voltage transformer
Amplitude corr. C 0.9000...1.1000 0.0001 1.0000 Phase C Voltage phasor magnitude correction
of an external voltage transformer
Division ratio 1000...20000 1 10000 Voltage sensor division ratio
Voltage input type 1=Voltage trafo
3=CVD sensor
1=Voltage trafo Type of the voltage input
Angle Corr A -20.0000...20.0000 deg 0.0001 0.0000 Phase A Voltage phasor angle correction of an
external voltage transformer
Angle Corr B -20.0000...20.0000 deg 0.0001 0.0000 Phase B Voltage phasor angle correction of an
external voltage transformer
Angle Corr C -20.0000...20.0000 deg 0.0001 0.0000 Phase C Voltage phasor angle correction of an
external voltage transformer
Table 8: Analog input settings, residual voltage
Parameter
Values (Range) Unit Step Default Description
Primary voltage
0.100...440.000
1)
kV 0.001 11.547 Primary voltage
Secondary voltage 60...210 V 1 100 Secondary voltage
Amplitude corr. 0.9000...1.1000 0.0001 1.0000 Amplitude correction
Angle correction -20.0000...20.0000 deg 0.0001 0.0000 Angle correction factor
1) In 9-2 applications, Primary voltage maximum is limited to 126 kV.