Table 9: Authorization settings
Parameter Values (Range) Unit Step Default Description
Remote Update 0=Disable
1=Enable
0=Disable Remote update
Secure Communication 0=False
1=True
1=True Secure Communication
Authority logging 1=None
2=Configuration
change
3=Setting group
4=Setting group,
control
5=Settings edit
6=All
1=None Authority logging level
Remote override
0=False
1)
1=True
2)
1=True Disable authority
Remote viewer (9-20
chars)
0 Set password (9-20 chars)
Remote operator (9-20
chars)
0 Set password (9-20 chars)
Remote engineer (9-20
chars)
0 Set password (9-20 chars)
Remote admin (9-20
chars)
0 Set password (9-20 chars)
Local override
0=False
3)
1=True
4)
1=True Disable authority
Local viewer (4-8 chars) 0 Set password (4-8 chars)
Local operator (4-8
chars)
0 Set password (4-8 chars)
Local engineer (4-8
chars)
0 Set password (4-8 chars)
Local admin (4-8 chars) 0 Set password (4-8 chars)
1) Authorization override disabled, communication tools ask password to enter the protection relay
2) Authorization override enabled, communication tools do not need password to enter the protection relay, except for WHMI which always requires
it
3) Authorization override disabled, LHMI password must be entered
4) Authorization override enabled, LHMI password is not asked
Table 10: Binary input settings
Parameter
Values (Range) Unit Step Default Description
Threshold voltage 16...176 Vdc 2 16 Digital input threshold voltage
Input osc. level 2...50 events/s 1 30 Digital input oscillation suppression threshold
Input osc. hyst 2...50 events/s 1 10 Digital input oscillation suppression hysteresis
1MAC059074-MB A Section 3
Basic functions
615 series ANSI 61
Technical Manual