Table 460: 87B Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Trip value 1.0...200.0 %In 1.0 5.0 Pickup value, percentage of the nominal
current
Minimum trip time 20...300000 ms 10 20 Minimum trip time
Table 461: 87B Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Table 462: 87B Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 10 20 Reset delay time
Table 463: 87C Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Trip value 1.0...200.0 %In 1.0 5.0 Pickup value, percentage of the nominal
current
Minimum trip time 20...300000 ms 10 20 Minimum trip time
Table 464: 87C Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Table 465: 87C Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 10 20 Reset delay time
Section 4 1MAC059074-MB A
Protection functions
566 615 series ANSI
Technical Manual