Table 978: Energizing inputs
Description Value
Rated frequency 50/60 Hz
Current inputs Rated current, I
n
0.2/1 A
1)2)
1/5 A
3)
Thermal withstand
capability:
Continuously 4 A 20 A
For 1 s 100 A 500 A
Dynamic current
withstand:
Half-wave value 250 A 1250 A
Input impedance <100 mΩ <20 mΩ
Voltage inputs Rated voltage 60...210 V AC
Voltage withstand:
Continuous 240 V AC
For 10 s 360 V AC
Burden at rated voltage <0.05 VA
1) Ordering option for residual current input
2) Not available for RET615
3) Ground current and/or phase current
Table 979: Energizing inputs (sensors)
Description
Value
Current sensor input Rated current voltage (in
secondary side)
75 mV...9000 mV
1)
Continuous voltage
withstand
125 V
Input impedance at 50/60
Hz
2...3 MΩ
2)
Voltage sensor input Rated voltage
6 kV...30 kV
3)
Continuous voltage
withstand
50 V
Input impedance at 50/60
Hz
3 MΩ
1) Equals the current range of 40...4000 A with a 80 A, 3 mV/Hz Rogowski
2) Depending on the used nominal current (hardware gain)
3) This range is covered (up to 2*rated) with sensor division ratio of 10 000:1
Section 14 1MAC059074-MB A
Technical data
1168 615 series ANSI
Technical Manual