Parameter Values (Range) Unit Step Default Description
Fourth reclose time 0...300000 ms 10 5000 Dead time for CBB4
Fifth reclose time 0...300000 ms 10 5000 Dead time for CBB5
Sixth reclose time 0...300000 ms 10 5000 Dead time for CBB6
Seventh reclose time 0...300000 ms 10 5000 Dead time for CBB7
Init signals CBB1 0...63 1 0 Initiation lines for CBB1
Init signals CBB2 0...63 1 0 Initiation lines for CBB2
Init signals CBB3 0...63 1 0 Initiation lines for CBB3
Init signals CBB4 0...63 1 0 Initiation lines for CBB4
Init signals CBB5 0...63 1 0 Initiation lines for CBB5
Init signals CBB6 0...63 1 0 Initiation lines for CBB6
Init signals CBB7 0...63 1 0 Initiation lines for CBB7
Shot number CBB1 0...5 1 0 Shot number for CBB1
Shot number CBB2 0...5 1 0 Shot number for CBB2
Shot number CBB3 0...5 1 0 Shot number for CBB3
Shot number CBB4 0...5 1 0 Shot number for CBB4
Shot number CBB5 0...5 1 0 Shot number for CBB5
Shot number CBB6 0...5 1 0 Shot number for CBB6
Shot number CBB7 0...5 1 0 Shot number for CBB7
Frq Op counter limit 0...250 1 0 Frequent operation counter lockout limit
Frq Op counter time 1...250 min 1 1 Frequent operation counter time
Frq Op recovery time 1...250 min 1 1 Frequent operation counter recovery time
Auto init 0...63 1 0 Defines INIT lines that are activated at auto
initiation
Table 911: 79 Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Manual close mode 0=False
1=True
0=False Manual close mode
Wait close time 50...10000 ms 50 250 Allowed CB closing time after reclose
command
Max wait time 100...1800000 ms 100 10000 Maximum wait time for haltDeadTime release
Max trip time 100...10000 ms 100 10000 Maximum wait time for deactivation of
protection signals
Max Thm block time 100...1800000 ms 100 10000 Maximum wait time for thermal blocking signal
deactivation
Cut-out time 0...1800000 ms 100 10000 Cutout time for protection coordination
Dsr time shot 1 0...10000 ms 100 0 Discrimination time for first reclosing
Dsr time shot 2 0...10000 ms 100 0 Discrimination time for second reclosing
Table continues on next page
Section 9 1MAC059074-MB A
Control functions
1028 615 series ANSI
Technical Manual