EasyManua.ls Logo

ABB 615 Series - Page 1142

ABB 615 Series
1196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The accuracy limit factors corresponding to the actual burden of the phase current
transformer to be used in differential protection fulfill the requirement.
F K Ik T e
a r dc
T T
m dc
> × × × × +
max
/
( ( ) )
ω
1 1
GUID-DA861DAD-C40E-4A82-8973-BBAFD15279C0 V1 EN (Equation 201)
Ik
max
The maximum through-going fault current (in I
R
) at which the protection is not allowed to trip
T
dc
The primary DC time constant related to Ik
max
ω The angular frequency, that is, 2*π*fn
T
m
The time-to-saturate, that is, the duration of the saturation free transformation
K
r
The remanence factor 1/(1-r), where r is the maximum remanence flux in p.u. from saturation flux
The accuracy limit factors corresponding to the actual burden of the phase current
transformer is used in differential protection.
The parameter r is the maximum remanence flux density in the CT core in p.u. from
saturation flux density. The value of the parameter r depends on the magnetic material
used and on the construction of the CT. For instance, if the value of r = 0.4, the remanence
flux density can be 40 percent of the saturation flux density. The manufacturer of the CT
has to be contacted when an accurate value for the parameter r is needed. The value r = 0.4
is recommended to be used when an accurate value is not available.
The required minimum time-to-saturate T
m
in 87T is half fundamental cycle period (10 ms
when fn = 50Hz).
Two typical cases are considered for the determination of the sufficient accuracy limit
factor (F
a
):
1. A fault occurring at the substation bus:
The protection must be stable at a fault arising during a normal operating situation.
Re-energizing the transformer against a bus fault leads to very high fault currents and
thermal stress and therefore re-energizing is not preferred in this case. Thus, the
remanence can be neglected.
The maximum through-going fault current Ik
max
is typically 10 I
r
for a substation
main transformer. At a short circuit fault close to the supply transformer, the DC time
constant (T
dc
) of the fault current is almost the same as that of the transformer, the
typical value being 100 ms.
Ik
max
10 I
r
T
dc
100 ms
ω 100π Hz
T
m
10 ms
Section 12 1MAC059074-MB A
Requirements for measurement transformers
1136 615 series ANSI
Technical Manual

Table of Contents

Other manuals for ABB 615 Series

Related product manuals