Description Value
• Control voltage range 20...250 V AC/DC
• Current drain through the supervision circuit ~1.5 mA
• Minimum voltage over the TCM contact 20 V AC/DC (15...20 V)
Table 985: Single-pole power output relays
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 8 A
Make and carry for 3.0 s 15 A
Make and carry for 0.5 s 30 A
Breaking capacity when the control-circuit time
constant L/R<40 ms, at 48/110/220 V DC
5 A/3 A/1 A
Minimum contact load 100 mA at 24 V AC/DC
Table 986: High-speed output HSO with BIO0007
Description
Value
Rated voltage 250 V AC/DC
Continuous contact carry 6 A
Make and carry for 3.0 s 15 A
Make and carry for 0.5 s 30 A
Breaking capacity when the control-circuit time
constant L/R <40 ms, at 48/110/220 V DC
5 A/3 A/1 A
Trip time <1 ms
Reset <20 ms, resistive load
Table 987: Ethernet interfaces
Ethernet interface
Protocol Cable Data transfer rate
Front TCP/IP
protocol
Standard Ethernet CAT 5 cable with RJ-45
connector
10 MBits/s
Rear TCP/IP
protocol
Shielded twisted pair CAT 5e cable with RJ-45
connector or fiber optic cable with LC connector
100 MBits/s
1MAC059074-MB A Section 14
Technical data
615 series ANSI 1171
Technical Manual