EasyManua.ls Logo

ABB 615 Series - Page 1179

ABB 615 Series
1196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description Value
Logic level 5 V TTL
Current consumption <4 mA
Power consumption <20 mW
1) According to the 200-04 IRIG standard
Table 992: Lens sensor and optical fiber for arc protection
Description Value
Fiber optic cable including lens 1.5 m, 3.0 m or 5.0 m
Normal service temperature range of the lens -40...+100°C
Maximum service temperature range of the lens,
max 1 h
+140°C
Minimum permissible bending radius of the
connection fiber
3.94 inches (100 mm)
Table 993: Degree of protection of flush-mounted protection relay
Description Value
Front side IP 54
Rear side, connection terminals IP 10
Left and right side IP 20
Top and bottom IP 20
Table 994: Environmental conditions
Description
Value
Operating temperature range -25...+55ºC (continuous)
Short-time service temperature range REF615, REG615, REM615 and RET615:
-40...+85ºC (<16 h)
1)2)
RED615: -40...+70ºC (<16 h)
1)2)
Relative humidity <93%, non-condensing
Atmospheric pressure 12.47...15.37 psi (86...106 kPa)
Altitude Up to 6561.66 feet (2000 m)
Transport and storage temperature range -40...+85ºC
1) Degradation in MTBF and HMI performance outside the temperature range of -25...+55 ºC
2) For relays with an LC communication interface the maximum operating temperature is +70 ºC
1MAC059074-MB A Section 14
Technical data
615 series ANSI 1173
Technical Manual

Table of Contents

Other manuals for ABB 615 Series

Related product manuals