GUID-18902907-5666-4AB6-80FD-BE875DFCBBD6-ANSI V1 EN
Figure 115: Configurable operating sectors
Table 237: Momentary per phase direction value for monitored data view
Criterion for per phase direction information
The value for DIR_A/_B/_C
The ANGLE_X is not in any of the defined sectors, or
the direction cannot be defined due too low
amplitude
0 = unknown
The ANGLE_X is in the forward sector 1 = forward
The ANGLE_X is in the reverse sector 2 = backward
(The ANGLE_X is in both forward and reverse
sectors, that is, when the sectors are overlapping)
3 = both
1MAC059074-MB A Section 4
Protection functions
615 series ANSI 239
Technical Manual