Parameter Values (Range) Unit Step Default Description
Curve parameter C 0.02...2.00 1 2.00 Parameter C for customer programmable
curve
Curve parameter D 0.46...30.00 1 29.10 Parameter D for customer programmable
curve
Curve parameter E 0.0...1.0 1 1.0 Parameter E for customer programmable
curve
Table 334: 50N,50G Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Minimum trip time 20...60000 ms 1 20 Minimum trip time for IDMT curves
Reset delay time 0...60000 ms 1 20 Reset delay time
Measurement mode 1=RMS
2=DFT
3=Peak-to-Peak
2=DFT Selects used measurement mode
IG/I0 signal Sel 1=Measured IG
2=Calculated I0
1=Measured IG Measured IG or calculated I0
Table 335: 50N-3,50G-3 Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Pickup value 1.00...40.00 xIn 0.01 1.00 Pickup value
Pickup value mult 0.8...10.0 0.1 1.0 Multiplier for scaling the pickup value
Trip delay time 20...200000 ms 10 20 Trip delay time
Table 336: 50N-3,50G-3 Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Table 337: 50N-3,50G-3 Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
IG/I0 signal Sel 1=Measured IG
2=Calculated I0
1=Measured IG Measured IG or calculated I0
1MAC059074-MB A Section 4
Protection functions
615 series ANSI 323
Technical Manual