RCA
= 0 deg
Non-operating area
Min forward angle
Min reverse angle
Min operate
current
Max forward angle
Max reverse angle
Forward
area
Backward
area
-VG
IG
GUID-A41E27BC-B5F2-4B8C-891D-BEF592013BEB V1 EN
Figure 158: Configurable operating sectors in phase angle characteristic
Table 351: Momentary operating direction
Fault direction
The value for DIRECTION
Angle between the polarizing and operating quantity
is not in any of the defined sectors.
0 = unknown
Angle between the polarizing and operating quantity
is in the forward sector.
1= forward
Angle between the polarizing and operating quantity
is in the reverse sector.
2 = backward
Angle between the polarizing and operating quantity
is in both the forward and the reverse sectors, that is,
the sectors are overlapping.
3 = both
1MAC059074-MB A Section 4
Protection functions
615 series ANSI 341
Technical Manual