Parameter Values (Range) Unit Step Default Description
Operating curve type 1=ANSI Ext Inv
2=ANSI Very Inv
3=ANSI Norm Inv
4=ANSI Mod Inv
5=ANSI DT
6=LT Ext Inv
7=LT Very Inv
8=LT Inv
9=IEC Norm Inv
10=IEC Very Inv
11=IEC Inv
12=IEC Ext Inv
13=IEC ST Inv
14=IEC LT Inv
15=IEC DT
17=Programmable
18=RI Type
19=RD Type
15=IEC DT Selection of time delay curve type
Trip delay time 50...200000 ms 10 50 Trip delay time
Characteristic angle -179...180 deg 1 -90 Characteristic angle
Max forward angle 0...180 deg 1 80 Maximum phase angle in forward direction
Max reverse angle 0...180 deg 1 80 Maximum phase angle in reverse direction
Min forward angle 0...180 deg 1 80 Minimum phase angle in forward direction
Min reverse angle 0...180 deg 1 80 Minimum phase angle in reverse direction
Voltage pickup value 0.010...1.000 xUn 0.001 0.010 Voltage pickup value
Table 358: 67/51N Group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Type of reset curve 1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate Selection of reset curve type
Operation mode 1=Phase angle
2=IoSin
3=IoCos
4=Phase angle 80
5=Phase angle 88
1=Phase angle Operation criteria
Enable voltage limit 0=False
1=True
1=True Enable voltage limit
Section 4 1MAC059074-MB A
Protection functions
354 615 series ANSI
Technical Manual