Name Type Values (Range) Unit Description
ANGLE_RCA FLOAT32 -180.00...180.00 deg Angle between polarizing and
operating quantity
ANGLE FLOAT32 -180.00...180.00 deg Angle between operating
angle and characteristic angle
I_OPER FLOAT32 0.00...40.00 xIn Calculated operating current
67/51N Enum 1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
Table 366: 67/50N Monitored data
Name Type Values (Range) Unit Description
FAULT_DIR Enum 0=unknown
1=forward
2=backward
3=both
Detected fault direction
PICKUP_DUR FLOAT32 0.00...100.00 % Ratio of pickup time / trip time
DIRECTION Enum 0=unknown
1=forward
2=backward
3=both
Direction information
ANGLE_RCA FLOAT32 -180.00...180.00 deg Angle between polarizing and
operating quantity
ANGLE FLOAT32 -180.00...180.00 deg Angle between operating
angle and characteristic angle
I_OPER FLOAT32 0.00...40.00 xIn Calculated operating current
67/50N Enum 1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
Section 4 1MAC059074-MB A
Protection functions
358 615 series ANSI
Technical Manual