Operationmode
Yo Bo Go
Settings:
•
Circleconductance
•
Circlesusceptance
•
Circleradius
Settings:
•
Susceptancereverse
•
SusceptancetiltAng
Settings:
•
Conductancereverse
•
ConductancetiltAng
Im(Yo)
Re(Yo)
Re(Y o)
Im( Yo)Im( Yo)
Re(Y o)
Notapplicableinhigh
resistancegroundedor
compensatesystems!
Notapplicablein
ungroundedsystems
Operationmode
Yo,Go Yo,Bo Go,Bo Yo,Go,Bo
Settings:
•
Circleconductance
•
Circlesusceptance
•
Circleradius
•
Conductancereverse
•
ConductancetiltAng
Settings:
•
Circleconductance
•
Circlesusceptance
•
Circleradius
•
Susceptancereverse
•
SusceptancetiltAng
Settings:
•
Conductancereverse
•
ConductancetiltAng
•
Susceptancereverse
•
SusceptancetiltAng
Settings:
•
Circleconductance
•
Circlesusceptance
•
Circleradius
•
Conductancereverse
•
ConductancetiltAng
•
Susceptancereverse
•
SusceptancetiltAng
Im(Yo) Im(Yo)
Re(Y o)
Im(Yo)
Re(Yo) Re(Yo)
Im(Yo)
Re(Y o)
GUID-B6939383-152A-4EE8-9C1A-3DFD01F6EA89 V1 EN
Figure 180: Admittance characteristic with different operation modes when
Directional mode = "Reverse"
Timer
Once activated, the timer activates the PICKUP output. The time characteristic is
according to DT. When the operation timer has reached the value set with the TRIP delay
1MAC059074-MB A Section 4
Protection functions
615 series ANSI 385
Technical Manual