Parameter Values (Range) Unit Step Default Description
Reference power 0.050...1.000 xPn 0.001 0.150 Reference value of residual power for
Wattmetric IDMT curves
Characteristic angle -179...180 deg 1 -90 Characteristic angle
Time multiplier 0.05...2.00 0.01 1.00 Time multiplier for Wattmetric IDMT curves
Operating curve type 5=ANSI DT
15=IEC DT
20=Wattmetric
IDMT
15=IEC DT Selection of time delay curve type
Trip delay time 60...200000 ms 10 60 Trip delay time for definite time
Table 402: 32N Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Table 403: 32N Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Measurement mode 1=RMS
2=DFT
3=Peak-to-Peak
2=DFT Selects used current measurement mode
Correction angle 0.0...10.0 deg 0.1 2.0 Angle correction
Min trip current 0.010...1.000 xIn 0.001 0.010 Minimum trip current
Min trip voltage 0.01...1.00 xUn 0.01 0.01 Minimum trip voltage
Reset delay time 0...60000 ms 1 20 Reset delay time
Pol reversal 0=False
1=True
0=False Rotate polarizing quantity
Io signal Sel 1=Measured IG
2=Calculated I0
1=Measured IG Selection for used Io signal
Vg or V0 1=Measured VG
2=Calculated V0
1=Measured VG Selection for used polarization signal
Section 4 1MAC059074-MB A
Protection functions
422 615 series ANSI
Technical Manual