GFCrelease
PICKUP
TRIP
Resettimer
Triptimer
Resetdelaytime Tripdelaytime
Pickupdelaytime
Pickupdelaytime
IG
VG
GUID-D2629C82-34BA-4E64-99E8-B3541D5016B4 V1 EN
Figure 216: Operation in “General EF” mode
Operation mode “Alarming EF” is applicable in all kinds of ground faults in ungrounded
and compensated networks, where fault detection is only alarming. It is intended to detect
ground faults regardless of their type (transient, intermittent or restriking, permanent, high
or low ohmic). The setting Voltage pickup value defines the basic sensitivity of the 67YN
function. In “Alarming EF” mode, the operate timer is started during the following
conditions.
Ground fault is detected by the GFC
Fault direction equals Directional mode setting
Estimated stabilized fundamental frequency residual current exceeds the set Min trip
current level
1MAC059074-MB A Section 4
Protection functions
615 series ANSI 451
Technical Manual

Table of Contents