GUID-74289FF5-E90D-4633-9FEE-04DB8E86A3AE V1 EN
Figure 227: Example of CT ratio correction setting calculation with in-zone
transformer
The rated load of the transformer is:
HV side (A): I
nT_A
= 5 MVA / (1.732 × 20 kV) = 144.3 A
LV side (A): I
nT_B
= 5 MVA / (1.732 × 10.5 kV) = 274.9 A
So the settings for CT ratio Corrections at HV (A) and LV (B) side are:
CT ratio Correction (A) = 200 A / 144.3 A = 1.386
CT ratio Correction (B) = 300 A / 274.9 A = 1.091
CT connections
The connections of the primary current transformers are designated as “Type 1” and
“Type 2”.
If the positive directions of the winding 1 and winding 2 protection relay currents are
opposite, the CT connection type setting parameter is “Type 1”. The connection
examples of “Type 1” are as shown in the
Figure 228 and Figure 229.
If the positive directions of the winding 1 and winding 2 protection relay currents
equate, the CT connection type setting parameter is “Type 2”. The connection
examples of “Type 2” are as shown in the Figure 230 and Figure 231.
The default value of the CT connection type setting is “Type 1”.
Section 4 1MAC059074-MB A
Protection functions
468 615 series ANSI
Technical Manual