• Transformer inrush currents
• Transformer overexcitation in overvoltage
• Underfrequency situations
• CT saturation at high currents passing through the transformer
The differential current caused by CT errors or tap changer positions increases at the same
percent ratio as the load current.
In the protection of generators, the false differential current can be caused by various
factors.
• CT errors
• CT saturation at high currents passing through the generator
GUID-0E927DF9-5641-4CAE-B808-0B75EA09EA95-ANSI V1 EN