EasyManua.ls Logo

ABB 615 Series - Page 558

ABB 615 Series
1196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
I_A
PICKUP
BLOCK
t
Timer
Level
detector
Blocking
logic
I_B
PICKUP
BLOCK
t
Timer
Level
detector
Blocking
logic
I_C
PICKUP
BLOCK
t
Timer
Level
detector
Blocking
logic
TRIP
TRIP
TRIP
GUID-B91E3EF5-7AB5-4F2D-AC6E-5A39FF7BC7B6 V1 EN
Figure 277: Functional module diagram
The module diagram illustrates all the phases of the function. Functionality for phases A,
B and C is identical.
All three phases have independent settings.
Level detector
The module compares differential currents I_A calculated by the peak-to-peak
measurement mode to the set Operate value. The Timer module is activated if the
differential current exceeds the value of the Operate value setting.
Timer
Once activated, Timer activates the PICKUP output. The time characteristic is according
to DT. When the operation timer reaches the value set by Trip delay time, the TRIP output
is activated. If the fault disappears before the module operates, the reset timer is activated.
Section 4 1MAC059074-MB A
Protection functions
552 615 series ANSI
Technical Manual

Table of Contents

Other manuals for ABB 615 Series

Related product manuals