EasyManua.ls Logo

ABB 615 Series - Page 585

ABB 615 Series
1196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Furthermore, the DC time constant (T
dc
) of the fault current is now smaller, assumed
to be 50 ms here.
Assuming the maximum fault current is 30 percent lower than in the bus fault and a
DC offset 90 percent of the maximum.
Ik
max
= 0.7 × 6 = 4.2 (I
R
)
T
dc
= 50 ms
ω = 100π Hz
T
m
= 10 ms
K
r
= 1/(1-0.4) = 1.6667
Equation 114 with these values gives the result:
F K Ik T e
a r dc
T
m
T
dc
> × × × × × +
max
. ( ( ) )0 9 1 1 24
ω
GUID-46A4591B-876D-4E32-A9AB-29F6C1657644 V2 EN
If the actual burden of the current transformer S
a
in the accuracy limit factor equation
cannot be reduced low enough to provide a sufficient value for F
a
, there are two
alternatives to deal with the situation.
1. A current transformer with a higher rated burden S
n
can be chosen (which also means
a higher rated accurate limit F
n
).
2. A current transformer with a higher nominal primary current I
1n
(but the same rated
burden) can be chosen.
Alternative 2 is more cost-effective and therefore often better, although the sensitivity of
the scheme is slightly reduced.
Example 2
Here the actions according to alternative 2 are taken to improve the actual accuracy limit
factor.
1MAC059074-MB A Section 4
Protection functions
615 series ANSI 579
Technical Manual

Table of Contents

Other manuals for ABB 615 Series

Related product manuals