example, horizontal communication between the protection relays, is only enabled by the
IEC 61850 communication protocol.
The protection relay utilizes Ethernet communication extensively for different purposes.
The exact services depend on the ordered product variant and enabled functionality.
HSR/PRP is available in 615 series Ver.5.0 FP1 ANSI.
HSR/PRP availability depends on the product ordering information. See
the Rear communication modules chapter for information on HSR/PRP
supported COM cards.
Table 4: TCP and UDP ports used for different services
Service Port
File Transfer Protocol (FTP and FTPS) 20, 21
IEC 61850 102
Web Server HTTP 80
Web Server HTTPS 443
Simple Network Time Protocol (SNTP) 123
Modbus TCP 502
DNP TCP 20000
The IEC 61850 communication implementation supports all monitoring and control
functions. Additionally, parameter setting and DFR records can be accessed using the IEC
61850 protocol. Oscillographic files are available to any Ethernet-based application in the
standard COMTRADE format. The protection relay can send and receive binary signals
from other devices (so-called horizontal communication) using the IEC 61850-8-1
GOOSE profile, where the highest performance class with a total transmission time of 3
ms is supported. Furthermore, the protection relay supports sending and receiving of
analog values using GOOSE messaging. The protection relay meets the GOOSE
performance requirements for tripping applications in distribution substations, as defined
by the IEC 61850 standard. The protection relay can simultaneously report events to five
different clients on the station bus.
The protection relay can support five simultaneous clients. If PCM600 reserves one client
connection, only four client connections are left, for example, for IEC 61850 and Modbus.
All communication connectors, except for the front port connector, are placed on
integrated optional communication modules. The protection relay can be connected to
Ethernet-based communication systems via the RJ-45 connector (100Base-TX) or the
fiber optic LC connector (100Base-FX).
1MAC059074-MB A Section 2
615 series overview
615 series ANSI 53
Technical Manual