Name Type Values (Range) Unit Description
I_ANGL_B1_C1 FLOAT32 -180.00...180.00 deg Current phase angle phase B
to C, line side
I_ANGL_C1_A1 FLOAT32 -180.00...180.00 deg Current phase angle phase C
to A, line side
I_ANGL_A2_B2 FLOAT32 -180.00...180.00 deg Current phase angle Phase
AB, neutral side
I_ANGL_B2_C2 FLOAT32 -180.00...180.00 deg Current phase angle Phase
BC, neutral side
I_ANGL_C2_A2 FLOAT32 -180.00...180.00 deg Current phase angle Phase
CA, neutral side
I_ANGL_A1_A2 FLOAT32 -180.00...180.00 deg Current phase angle diff
between line and neutral side,
Phase A
I_ANGL_B1_B2
FLOAT32 -180.00...180.00 deg Current phase angle diff
between line and neutral side,
Phase B
I_ANGL_C1_C2
FLOAT32 -180.00...180.00 deg Current phase angle diff
between line and neutral side,
Phase C
87G
Enum 1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
IA-diff FLOAT32 0.00...80.00 Measured differential current
amplitude phase IA
IB-diff FLOAT32 0.00...80.00 Measured differential current
amplitude phase IB
IC-diff FLOAT32 0.00...80.00 Measured differential current
amplitude phase IC
IA-bias FLOAT32 0.00...80.00 Measured bias current
amplitude phase IA
IB-bias FLOAT32 0.00...80.00 Measured bias current
amplitude phase IB
IC-bias FLOAT32 0.00...80.00 Measured bias current
amplitude phase IC
Section 4 1MAC059074-MB A
Protection functions
586 615 series ANSI
Technical Manual