This CB mode can be used in soft-started or slip ring motors for protection against a large
starting current, that is, a problem in starting and so on.
GUID-DDAD7B3F-28BE-4573-BE79-FBB488A22ECA V1 EN
GUID-1470A4DB-310F-46BC-B775-843EAB8BA836 V1 EN
Figure 378: Functionality of start-up supervision in the "IIt, CB" mode and the "IIt and
stall, CB" mode
The Str over delay time setting has different purposes in different modes of operation.
In the “IIt” or “IIt & stall” modes, the aim of this setting is to check for the completion
of the motor start-up period. The purpose of this time delay setting is to allow for short
interruptions in the current without changing the state of the MOT_START output. In
1MAC059074-MB A Section 4
Protection functions
615 series ANSI 753