For example, six setting groups can be controlled with three binary inputs. The SG
operation mode is set to “Logic mode 2” and inputs BI_SG_2 and BI_SG_5 are
connected together the same way as inputs BI_SG_3 and BI_SG_6.
Table 35: SG operation mode = “Logic mode 1”
Input
BI_SG_2 BI_SG_3 BI_SG_4 BI_SG_5 BI_SG_6 Active group
FALSE FALSE FALSE FALSE FALSE 1
TRUE FALSE FALSE FALSE FALSE 2
any TRUE FALSE FALSE FALSE 3
any any TRUE FALSE FALSE 4
any any any TRUE FALSE 5
any any any any TRUE 6
Table 36: SG operation mode = “Logic mode 2”
Input
BI_SG_2 BI_SG_3 BI_SG_4 BI_SG_5 BI_SG_6 Active group
FALSE FALSE FALSE any any 1
TRUE FALSE FALSE any any 2
any TRUE FALSE any any 3
any any TRUE FALSE FALSE 4
any any TRUE TRUE FALSE 5
any any TRUE any TRUE 6
The setting group 1 can be copied to any other or all groups from HMI (Copy group 1).