Parameter Values (Range) Unit Step Default Description
High trigger
level
0.00...60.00 pu 0.01 10.00 High trigger
level for the
analog channel
Low trigger
level
0.00...2.00 pu 0.01 0.00 Low trigger
level for the
analog channel
Storage mode
0=Waveform
1=Trend / cycle
1 0 Storage mode
for the analog
channel
1) Recordable values are available only in trend mode. In waveform mode, samples for this signal type are
constant zeroes. However, these signal types can be used to trigger the recorder on limit violations of the
corresponding analog channel.
Table 851: DFR Non-group binary channel settings
Parameter Values (Range) Unit Step Default Description
Operation 1=Enable
5=Disable
1 5=Disable Binary channel
is enabled or
disabled
Level trigger
mode
1=Positive or
Rising
2=Negative or
Falling
3=Both
4=Level trigger
off
1 1=Rising Level trigger
mode for the
binary channel
Storage mode
0=Waveform
1=Trend / cycle
1 0 Storage mode
for the binary
channel
Channel id text
0 to 64
characters,
alphanumeric
DR binary
channel X
Identification
text for the
analog channel
used in the
COMTRADE
format
Table 852: DFR Control data
Parameter
Values (Range) Unit Step Default Description
Trig recording 0=Cancel
1=Trig
Trigger the
disturbance
recording
Clear
recordings
0=Cancel
1=Clear
Clear all
recordings
currently in
memory
Section 8 1MAC059074-MB A
Measurement functions
948 615 series ANSI
Technical Manual

Table of Contents

Other manuals for ABB 615 Series

Related product manuals