Object 0x1400/0x1401/0x1402 COB-ID
= PDO non-existent/not valid
RxPDO1 factory setting = valid
RxPDO2/3 factory setting = not valid
Object 0x1400/0x1401/0x1402 transmission type
Update RxPDO data on each SYNC
Update RxPDO data on each SYNC
Event driven (manufacturer specific)
Event driven (profile specific) default value
Values 254 & 255 are handled identically. Update RxPDO data on each Rx.
The inhibit time for RxPDO is
without function. Values can be entered, but are without
further function.
The event time is used as monitoring function for RxPDO’s. If during the set time no
RxPDO is received, one of the following faults is triggered:
202A Fault RxPDO1
202B Fault RxPDO2
CB: Control byte SI: Sub Index All values in hexadecimal without leading 0x
*
Note, that Object 1400/1 Highest has to be deactivated first for the correct Write
access for Object 1400/2.
04/13 CM-CAN ACU 67