EasyManuals Logo

BONFIGLIOLI Vectron Active Cube User Manual

BONFIGLIOLI Vectron Active Cube
240 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #78 background imageLoading...
Page #78 background image
12.3.1.3 Examples of reading parameters
Example 1
Read parameter Rated speed 372 (type: uint) in data set 2 with the current parame-
ter value 1460.
Index = 372 + 0x2000 = 0x2174, value = 1460 = 0x05B4
Client Server
SDO Upload (expedited)
0
1
2
3
4
5
6
7
COB ID
Control byte
Index
Subindex
Data
0x601
0x40
0x74
0x21
0x02
--
--
--
--
Server Client
Upload Response
0
1
2
3
4
5
6
7
COB ID
Control byte
Index
Subindex
Data
0x581
0x4B
0x74
0x21
0x02
0xB4
0x05
--
--
Example 2
Read parameter Warning Limit Heat Sink Temp. 407 (type: int) in data set 0 with the
current parameter value -5.
Index = 407 + 0x2000 = 0x2197, value = -5 = 0xFFFB
Client Server
SDO Upload (expedited)
0
1
2
3
4
5
6
7
COB ID
Control byte
Index
Subindex
Data
0x601
0x40
0x97
0x21
0x00
--
--
--
--
Server Client
Upload Response
0
1
2
3
4
5
6
7
COB ID
Control byte
Index
Subindex
Data
0x581
0x4B
0x97
0x21
0x00
0xFB
0xFF
--
--
Example 3
Read parameter Fixed Frequency 1 480 (type: long) in data set 1 with the current
parameter value 75.00 Hz.
Index = 480 + 0x2000 = 0x21E0, value = 7500 = 0x00001D4C
Client Server
SDO Upload (expedited)
0
1
2
3
4
5
6
7
COB ID
Control byte
Index
Subindex
Data
0x601
0x40
0xE0
0x21
0x01
--
--
--
--
Server Client
Upload Response
0
1
2
3
4
5
6
7
COB ID
Control byte
Index
Subindex
Data
0x581
0x43
0xE0
0x21
0x01
0x4C
0x1D
0x00
0x00
78 CM-CAN ACU 04/13

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the BONFIGLIOLI Vectron Active Cube and is the answer not in the manual?

BONFIGLIOLI Vectron Active Cube Specifications

General IconGeneral
BrandBONFIGLIOLI
ModelVectron Active Cube
CategoryDC Drives
LanguageEnglish

Related product manuals