23
Description ToolboxST application detects a major difference in [ ] controller application code
Possible Cause
Compressing variables, EGD pages, distributed I/O, or NVRAM
Changing frame or background period
Changing controller or network redundancy
Changing controller platform or NTP client mode
Changing controller host name or IP address
Changing IONet IP address
Adding/removing first/last linking device (PFFA), respectively
Removing a WCBM module
Changing from multicast to broadcast (vice-versa) I/O communication
Adding the first shared I/O module or connecting the first Controller to Controller I/O variable
Removing the last Modbus Slave point
Disabling controller web pages
Disabling Wind Compress Data Log
Disabling Wind Farm Management System
Solution Rebuild the controller and download.
Note This alarm is not reported to the WorkstationST Alarm Viewer. This alarm is generated by the ToolboxST application,
not by the I/O pack or module.