Description Outputs unhealthy on IONet [ ] - Minor Signature Mismatch
Possible Cause Application/configuration does not match in I/O pack or module and controller
Solution
Rebuild and download the application/parameters to all the controllers and I/O packs or modules.
Reload the firmware and the parameters to the affected I/O pack or module.
Reload the firmware and the application to all the controllers.
If the problem persists, replace affected I/O pack or module, then replace the controller.
1008-1010,
1264-1266
Description Outputs unhealthy on IONet [ ] - Timestamp Mismatch
Possible Cause Application/configuration does not match in I/O pack or module and controller
Solution
Rebuild and download the application/parameters to all the controllers and I/O packs or modules.
Reload the firmware and the parameters to the affected I/O pack or module.
Reload the firmware and the application to all the controllers.
If the problem persists, replace affected I/O pack or module, then replace the controller.
Common I/O Module Functionality GEH-6855_Vol_II System Guide 475