1000-2024
Description Inputs unhealthy on IO Module [ ], T pack IONet [ ] - Message Length not valid
Possible Cause Application/configuration does not match in the I/O pack and controller.
Solution
• Rebuild and download application/parameters to all controllers and I/O packs.
• Reload firmware and parameters to the affected I/O pack.
• Reload firmware and application to all controllers.
• If problem persists, replace affected I/O pack, then replace controller.
1000-2024
Description Inputs unhealthy on IO Module [ ], IONet [ ] - Message Length not valid
Possible Cause Application/configuration does not match in the I/O pack and controller.
Solution
• Rebuild and download application/parameters to all controllers and I/O packs.
• Reload firmware and parameters to the affected I/O pack.
• Reload firmware and application to all controllers.
• If problem persists, replace affected I/O pack, then replace controller.
1000-2024
Description Inputs unhealthy on IO Module [ ], R Pack IONet [ ] - Major Signature Mismatch
Possible Cause Application/configuration does not match in the I/O pack and controller.
Solution
• Rebuild and download application/parameters to all controllers and I/O packs.
• Reload firmware and parameters to the affected I/O pack.
• Reload firmware and application to all controllers.
• If problem persists, replace affected I/O pack, then replace controller.
76 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II