Parameter
Address Name / seng range / [default seng] Info
0x2D4D:001 Motor ulisaon (i²xt) - specic
characterisc: x1 =
n01/nN (n01 ~ 0)
0 ... [0] ... 600 %
User-denable characterisc for speed-dependent evaluaon of the
motor current.
0x2D4D:002 Motor ulisaon (i²xt) - specic characterisc: y1 =
i01/iN (x1)
0 ... [100] ... 600 %
0x2D4D:003 Motor ulisaon (i²xt) - specic
characterisc: x2 =
n02/nN (n02 = limit reduced cooling)
0 ... [0] ... 600 %
0x2D4D:004 Motor ulisaon (i²xt) - specic characterisc: y2 =
i02/iN (x2)
0 ... [100] ... 600
%
0x2D4D:005 Motor ulisaon (i²xt) - specic characterisc: x3 =
n03/nN (n03 = rated speed)
0 ... [100] ... 600 %
0x2D4D:006 Motor ulisaon (i²xt) - specic characterisc: y3 =
i03/iN (x3)
0 ... [100] ... 600 %
0x2D4D:007 Motor ulisaon (i²xt) - specic characterisc: x4 =
n04/nN (n04 = limit eld weakening)
0 ... [100] ... 600 %
0x2D4D:008 Motor ulisaon (i²xt) - specic characterisc: y4 =
i04/iN (x4)
0 ... [100] ... 600 %
Conguring the motor control
Mot
or protecon
Motor overload monitoring (i²*t)
294